Einzelheiten zu den Produkten

Created with Pixso. Zu Hause Created with Pixso. Produits Created with Pixso.
Transformer Testers
Created with Pixso.

Anti Interference Transformer Dielectric Loss Tester Variable Frequency Technology

Anti Interference Transformer Dielectric Loss Tester Variable Frequency Technology

Markenbezeichnung: Or-electric
Modellnummer: Ord (b)
MOQ: 1 Satz
Price: 2570~3860 USD/set
Zahlungsbedingungen: D/P, T/T, Western Union, MoneyGram
Versorgungsfähigkeit: 150 Sätze/Jahr
Einzelheiten
Herkunftsort:
WUHAN, CHINA
Zertifizierung:
ISO9001,ISO14001,ISO45001
Kapazitätsmessbereich:
3pF~1μF
Verlustmessbereich:
0~100 % unbegrenzt
Fehler bei der maximalen Kapazität:
±(1,0 %×rd±1 pF)
Maximaler Verlustfehler:
±(1,0 %×rd±0,04 %)
Kapazität min. Auflösung:
0,001 pF
Verlust-Mindestauflösung:
0.001%
Prüfstrom:
10μA~5A
Interne Ausgangsspannung:
0,5~10kV
Interner Ausgangsstrom:
200 mA
Stromversorgung:
180V~270VAC,50Hz/60Hz ±1%
Größe:
430 mm × 310 mm × 345 mm
Gewicht:
270,6 kg
Garantie:
1 Jahr
Hs-Code:
9030841000
Verpackung Informationen:
Papierpaket
Lieferzeit:
6 Arbeits-Tage
Hervorheben:

Transformer Dielectric Loss Tester

,

Anti Interference Dielectric Loss Tester

Beschreibung des Produkts

ORD(B) Anti-interference Dielectric Loss Tester


I. Product introduction

ORD(B) Anti-interference dielectric loss tester adopts variable frequency power supply technology and utilizes single-chip micro-controllers and electronic technology for automatic frequency conversion, analog-to-digital conversion, and data operation. The instrument has strong anti-interference ability, fast testing speed, high accuracy, and easy operation.


II. Features

● The instrument has high measurement accuracy and can meet the requirements of oil dielectric loss measurement. Therefore, only a standard oil cup and a dedicated testing line are needed to achieve oil dielectric loss measurement.

● By using frequency conversion technology to eliminate on-site 50Hz power frequency interference, reliable data can be measured even in strong electromagnetic interference environments.

● The over-current protection function ensures that the instrument is not damaged in the event of a short circuit or breakdown of the test sample.

● Comes with standard capacitors and high-voltage power supply for easy on-site testing and reduces on-site wiring.

● The instrument adopts a large screen LCD display, and the testing process is both intuitive and easy to operate through Chinese character menu prompts.


III. Technical parameters

Measurement range

capacity

3pF~60000 pF/10kV

60pF~1μF/0.5kV

dielectric loss

0~100% unlimited

 (automatic identification of capacitance,

inductance, and resistance test samples)

Max error

capacity

±(1.0%×rd±1 pF)

dielectric loss

±(1.0%×rd±0.04%)

Resolution

capacity

Min 0.001 pF

dielectric loss

Min 0.001 %

Test current

10μA~5A

Internal output HV

set voltage range

0.5~10kV

max output current

200mA

Test frequency

50Hz single-frequency,45/55Hz Automatic dual frequency conversion

Power supply

180V~270VAC,50Hz/60Hz ±1%

Environment

TEMP

0~40℃

RH

≤ 90%(no condensation)

Size

430mm×310mm×345mm

Weight

27.6 kg


IV. Warranty period & after-sale service

● The warranty period for the products supplied by the supplier is 12 months from the date of product acceptance or 15 months from the date of the last piece of equipment arrival, whichever comes first. Within the warranty period, the supplier shall provide free services to the purchaser; After the warranty period, the supplier will only charge a cost fee for the expenses incurred in repairing the equipment.