| Brand Name: | Or-electric |
| Model Number: | OR6F |
| MOQ: | 1 set |
| Price: | 25000~37500 USD/set |
| Payment Terms: | D/P,T/T |
| Supply Ability: | 170 sets/year |
OR6F Relay Protection Tester
I. Product introduction
The OR6F relay protection tester is powered by a high-performance DSP+FPGA control system and features built-in Windows platform software, enabling operation either as a standalone unit or in conjunction with an external computer. It employs high-fidelity, high-reliability modular linear power amplifiers to deliver smooth output waveforms. The tester can output standard six-phase voltage and six-phase current, and includes a dedicated internal DC output power supply. It offers a wide range of digital I/O configurations, featuring 10 channel contact inputs and 8 pairs of open contacts outputs. Additionally, it is equipped with a GPS interface, allowing for synchronized testing between multiple units. Its compact size, high precision, and comprehensive protection capabilities further enhance the instrument's cost-performance ratio.
Ⅱ.Technical parameters
|
AC current output |
Output accuracy |
Grade 0.1 |
|
|
Output per phase (RMS value) of the six-phase current |
0~30A |
||
|
Output per phase (RMS value) of three-phase current |
0~60A |
||
|
6. DC current output (RMS) |
0~180A |
||
|
Permissible long-term operating value of line current (RMS) |
10A |
||
|
Maximum output power of the phase current |
450VA |
||
|
6. Maximum output power at maximum current output |
1000VA |
||
|
6. Maximum allowable operating time at maximum current output |
10s |
||
|
Frequency range (fundamental frequency) |
0~1200Hz |
||
|
harmonic number |
0–24 times |
||
|
DC current output |
output accuracy |
Grade 0.2 |
|
|
Current output |
0–±10 A per phase, 0–±60 A for 6 parallel circuits |
||
|
Maximum output load voltage |
20V |
||
|
AC voltage output |
output accuracy |
Grade 0.1 |
|
|
Phase voltage output (RMS) |
0~120V |
||
|
Line voltage output (RMS) |
0~240V |
||
|
Phase voltage / line voltage output power |
80VA / 100VA |
||
|
Frequency range (fundamental frequency) |
0~1200Hz |
||
|
harmonic number |
0–24 times |
||
|
DC voltage output |
output accuracy |
Grade 0.2 |
|
|
Line voltage output amplitude |
0~±160V |
||
|
Line voltage output amplitude |
0~±320V |
||
|
Phase voltage / line voltage output power |
70VA / 140VA |
||
|
Digital signal and time measurement |
on-off input |
Route 10 |
Dry contact: 1–20 mA, 24 V Potential contacts: "0": 0–+6 V; "1": +11 V–+250 V |
|
Digital output |
8 pairs |
DC:220V/0.2A;AC:220V/0.5A |
|
|
time measurement |
measuring range |
0.1ms ~ 9999s |
|
|
certainty of measurement |
0.1ms |
||
Ⅲ.Warranty period & after-sale service
● The warranty period for the products supplied by the supplier is 12 months from the date of product acceptance or 15 months from the date of the last piece of equipment arrival, whichever comes first. Within the warranty period, the supplier shall provide free services to the purchaser; After the warranty period, the supplier will only charge a cost fee for the expenses incurred in repairing the equipment.
● All products come with lifetime maintenance services.
Ⅳ.Company profile
![]()