rango de medición de resistencia:
0 ̊200Ω
Rango de medición de voltaje:
CA 0~19,99 V
Precisión de resistencia mínima:
≤±1,5%±1d
exactitud del voltaje:
≤±3%±1d
Resolución de resistencia mínima:
0.001Ω
Resolución del voltaje:
0.01V
Fuente de alimentación de CA:
220v/50hz
Fuente de alimentación de corriente continua:
8 pilas de 1,5 V (AA, R6)
Ambiente:
0℃~+45℃,≤85%RH
Tamaño:
220 mm × 200 mm × 105 mm
Peso:
≤1.4 kg
Garantía:
1 año
Código Hs:
9030332000
Detalles de empaquetado:
paquete de papel
Tiempo de entrega:
3 días de trabajo
Resaltar:

Earth Test Equipment 200Ω

,

Portable Earth Test Equipment

,

200Ω Earth Resistance Tester

Descripción del producto

ORGR-D Earth Resistance Tester


I.Product introduction

ORGR-D earth resistance tester uses an internal DC/AC converter to convert DC into AC low-frequency constant current, which forms a circuit through the auxiliary grounding electrode C and the tested object E. An AC voltage drop is generated on the tested object, amplified by the AC amplifier through the auxiliary grounding electrode P, and then detected and displayed on the meter head. With the help of a multiplier switch, three different measurement limits can be obtained: 0-2 Ω, 0-20 Ω, and 0-200 Ω.


II. Technical parameters

Measurement range & constant current(RMS)

Resistance

10mA

0~2Ω

10mA

2~20Ω

1mA

20~200Ω

Voltage

AC  0~19.99V

Accuracy

0~0.2Ω≤±3%±1d

0.2Ω~199.9Ω≤±1.5%±1d

1~19.99V≤±3%±1d

Resolution

0.001Ω,0.01Ω,0.1Ω,0.01V

Measurement error

Allowable auxiliary grounding resistance RC(Between C1 and C2)

0~2Ω,2~20Ω  ≤1kΩ

20~200Ω  ≤2kΩ

RP(between P1 and P2)<40k

Allowable ground voltage(RMS)

≤5V

Error

≤±5%

Power supply

DC

8×1.5V(AA,R6)batteries

AC

220V/50Hz

Environment

0℃~+45℃,≤85%RH

Size

220mm×200mm×105mm

Weight

≤1.4kg


III. Warranty period & after-sale service

● The warranty period for the products supplied by the supplier is 12 months from the date of product acceptance or 15 months from the date of the last piece of equipment arrival, whichever comes first. Within the warranty period, the supplier shall provide free services to the purchaser; After the warranty period, the supplier will only charge a cost fee for the expenses incurred in repairing the equipment.
● All products come with lifetime maintenance services.


IV. Company profile